Breaker Analysis

Options

The test system can be extended by the addition of optional components such as voltage sources and can be customized by the inclusion of customer-specific connection panels. 

Evaluation Unit

 19" industrial standard, integrated in the front panel of the cabinet, consisting of:

  1. Industrial PC (Windows XP operating system, pre-installed user software)
  2.  17" TFT monitor
  3. industrial rackmount keyboard/mouse unit

 height: 13 HU 

Sources

The additional current and voltage sources can be used to supply external actuators such as spring-tensioning motors, release and operating coils or heating systems.

The outputs of all sources are located on a connection panel and external sources can be looped in if required. The sources are released via integrated power contactors.

All sources can be controlled and monitored either manually or automatically by the test system. The desired values are set automatically in accordance with the parameters of the test plan. The sources can be controlled either statically or dynamically, e.g. to test overcurrent or undervoltage releases.

  Parameters Required I/O channels  
Electronic DC voltage source SM 300-10 Power 3000 W
Voltage 0 to 300 VDC
Max. current 10 A

1 relay output
1 analog actuating signal

3 U
Electronic DC voltage source SM 300-20 Power 6000 W
Voltage 0 to 300 VDC
Max. current 20 A
1 relay output
1 analog actuating signal
4 U
AC/DC voltage source
EPOS CV 20.1
Power 5400 VA
Voltage 0 to 270 V
Max. current 20 AAC/ADC
2 relay outputs
1 analog actuating signal
1 analog feedback channel
4 U
AC/DC voltage source
EPOS CV 45.1
Power 8100 VA
Voltage 0 to 270 V
Max. current 30 AAC/ADC
2 relay outputs
1 analog actuating signal
1 analog feedback channel
4 U

Process Interfaces

Coil circuit extension  Extension to 4 OPEN coil circuits and 4 CLOSE coil circuits Required I/O channels:
1 relay output

 

-
Patch panel on the cabinet front  2 x 108-pole  The patch panel is used to allocate the inputs and outputs of the test system to the appropriate connection leads of the test object. The allocation is made using industrial plug connectors with the appropriate wiring (allocation) inside the plug housing.  5 U
Custom connection panel on the cabinet front    Connection panel for connecting the measurement and output signals for coil control, for example, the main and auxiliary contacts and analog or incremental sensors. Connections are made using safety banana sockets and multi-contact sensor sockets. The exact specifications are agreed with individual customers.  5 U
Binary I/O extension  24 V to 300 VDC  Addition of:
12 universal binary inputs with a common ground

8 binary outputs
- -